Description
SPECS
General Specifications | |
Input Connection |
Terminal Block |
Output Connection |
1″> 6 foot line cords ready for hard wiring to UPS terminal block Terminal Block |
PTS Transfer Time |
1″> < 65 ms Buck & Boost mode < 10ms |
Frequency |
60Hz ±3Hz |
Input Specifications | |
Step Load Response |
1/2 Cycle Full Recovery (Full resistive load) |
Short Circuit Protection |
15A Circuit Breaker |
Battery String Voltage |
48VDC (Four 12VDC Battery) |
Voltage Range |
100~130VAC (120VAC Nominal) Prog. 90-150VAC |
Current Capacity |
30A |
Physical Specifications | |
Width |
1″> 4.75″ 120.6mm |
Height |
1″> 4.6″ 116.8mm |
Depth |
1″> 6.5″ 165mm |
Weight |
7 lbs |
Output Specifications | |
Load Crest Factor |
3:1 (Max) |
Power VA/W |
2000VA/1500W |
Output Voltage |
100~130 +/- 2VAC |
Overload Capacity |
110% for 3 minutes |
Output Waveform |
Sine Wave |
Inverter Mode |
120VAC +/- 5% |
Output Waveform THD |
< 3% (Resistive Load) |
Power Factor |
0.75 |
Mechanical Specifications | |
Mounting |
Rack Mount EARS, 4 points optional 19″ rack mount |
Environmental Specifications | |
Storage Temperature Range |
-50°C to 75°C |
Altitude (Note 2) |
10,000ft/3,000m |
Cooling |
Convection (Approx. 7 with contractor coil dissipation) |
Operating Temperature |
-34°C to +74°C |
Operating Humidity Level |
0-95% Non Condensing |
Safety Standard Specifications | |
Surge Immunity |
IEC 1000-4-5 |
EMI |
FCC Class A |