Physical Characteristics (Overall)
AWG |
Material |
No. of Pairs |
2.5 mm² |
BC – Bare Copper |
1 |
Type |
Material |
Tape |
Mica Glass Tape |
|
XLP, XLPO, XLPE (Thermoset) |
Number |
Color |
1 |
Blue & Black |
Type |
Material |
Coverage [%] |
Tape |
Polyester |
100% |
Material |
Nominal Diameter |
LSZH – Low Smoke Zero Halogen (Flame Retardant) |
10.7mm |
Electrical Characteristics
Nominal Conductor DCR |
7.56 Ohm/km |
Nom. Capacitance Conductor to Conductor |
150 pF/m |
Nominal Inductance |
?1 mH/km |
Temperature Range
Operating Temperature Range: |
-30°C to 90°C (EN) |
Mechanical Characteristics
Bulk Cable Weight: |
132 kg/km |
Standards
Other Standards: |
EN 50288-7 |
Applicable Environmental and Other Programs
EU Directive 2000/53/EC (ELV): |
Yes |
EU Directive 2003/96/EC (BFR): |
Yes |
EU Directive 2011/65/EU (RoHS 2): |
Yes |
EU Directive 2012/19/EU (WEEE): |
Yes |
EU Directive 2015/863/EU (RoHS 2 amendment): |
Yes |
MII Order #39 (China RoHS): |
Yes |
Suitability
Suitability – Oil Resistance: |
Yes |
Suitability – Sunlight Resistance: |
Yes |
Flammability, LS0H, Toxicity Testing
IEC Flammability: |
IEC 60332-1-2, IEC 60332-3-24 |
Other Flammability: |
BS 6387 CWZ |
IEC 60754-1 – Halogen Amount: |
0.005 |
IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity: |
10 µS/mm |
IEC 60754-2 – Halogen Acid Gas Amount – Min. pH: |
4.3 |
IEC 61034-2 – Smoke Density Min. Transmittance: |
60% |
History
Update and Revision: |
Revision Number: 0.29 Revision Date: 02-15-2024 |