ZA29HKF02 – 2P0.5mm2 XLP/OS/LSZH B1 Fire Resistance cable

Call for Price

Compare

Description

Product Overview

Suitable Applications: For Control Applications up to 300V

Construction Details

Conductor
Element No. of Elements Size Material Notes
Conductor(s) 4 0.5 mm² BC – Bare Copper Mica tape wrapped over the conductors
Insulation
Material Color Code
XLPE Black 1, White 1, Black 2, White 2
Outer Shield
Shield Type Material Coverage Notes
Tape Bi-Laminate (Alum+Poly) 100% ATC drain wire placed along with Overall Foil shield
Table Notes: All pairs laid up together & binded by Non-woven tape binder
Outer Jacket
Material
LSZH – Low Smoke Zero Halogen (Flame Retardant)
Overall Cable Diameter (Nominal): 12.0 mm (0.472 in)

Electrical Characteristics

Electricals
Max. Conductor DCR
36.72 ?/km @ 20°C
Voltage
Voltage Rating
300 V

Mechanical Characteristics

Temperature
Operating
-30°C To +90°C
Bulk Cable Weight: 130 kg/km (87 lbs/1000ft)

Standards and Compliance

Flammability / Reaction to Fire: IEC 60332-1-2, IEC 60331-21, BS 6387 CWZ , SS 299-1
GB Compliance: GB 31247 B1 (d0, t1, a1)
ISO/IEC Compliance: Smoke Density as per IEC 61034-2
European Halogen Free Standards: IEC 60754-1 – Halogen Amount = 0.5%, IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity = 4.3 , IEC 60754-2 – Halogen Acid Gas Amount – Min. pH = 10

Product Notes

Notes: EN 50228-7, IEC 60332-3C

History

Update and Revision: Revision Number: 0.10 Revision Date: 11-08-2023