Description
Product Overview
| Suitable Applications: | For Control Applications up to 300V |
Construction Details
Conductor
| Element | No. of Elements | Size | Material | Notes |
|---|---|---|---|---|
| Conductor(s) | 4 | 0.5 mm² | BC – Bare Copper | Mica tape wrapped over the conductors |
Insulation
| Material | Color Code |
|---|---|
| XLPE | Black 1, White 1, Black 2, White 2 |
Outer Shield
| Shield Type | Material | Coverage | Notes |
|---|---|---|---|
| Tape | Bi-Laminate (Alum+Poly) | 100% | ATC drain wire placed along with Overall Foil shield |
| Table Notes: | All pairs laid up together & binded by Non-woven tape binder |
Outer Jacket
| Material |
|---|
| LSZH – Low Smoke Zero Halogen (Flame Retardant) |
| Overall Cable Diameter (Nominal): | 12.0 mm (0.472 in) |
Electrical Characteristics
Electricals
| Max. Conductor DCR |
|---|
| 36.72 ?/km @ 20°C |
Voltage
| Voltage Rating |
|---|
| 300 V |
Mechanical Characteristics
Temperature
| Operating |
|---|
| -30°C To +90°C |
| Bulk Cable Weight: | 130 kg/km (87 lbs/1000ft) |
Standards and Compliance
| Flammability / Reaction to Fire: | IEC 60332-1-2, IEC 60331-21, BS 6387 CWZ , SS 299-1 |
| GB Compliance: | GB 31247 B1 (d0, t1, a1) |
| ISO/IEC Compliance: | Smoke Density as per IEC 61034-2 |
| European Halogen Free Standards: | IEC 60754-1 – Halogen Amount = 0.5%, IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity = 4.3 , IEC 60754-2 – Halogen Acid Gas Amount – Min. pH = 10 |
Product Notes
| Notes: | EN 50228-7, IEC 60332-3C |
History
| Update and Revision: | Revision Number: 0.10 Revision Date: 11-08-2023 |