NH50106ASFB – DataTuff™ Industrial Ethernet CAT6A 4x2x23AWG/1 S/FTP SWB Fire Resistant (PH120)

Call for Price

Compare

Description

Product Overview

Suitable Applications: Industrial Ethernet Cat 6A connection with Fire Resistant capability

Construction Details

Conductor
Size Stranding Stranding Class Material No. of Pairs No. of Elements
23 AWG Solid Class 1 BC – Bare Copper 4 8
Insulation
Material Nom. Insulation Diameter Color Code Notes
PE – Polyethylene 1.58 mm (0.0622 in) Blue & White with Blue Strips, Orange & White with Orange Strips, Green & White with Green Strips, Brown & White with Brown Strips Fire Protection Barrier: Mica glass Tape(MGT)
Inner Shield
Element Shield Type Material Notes
Individual Pair Tape Bi-Laminate (Alum+Poly) All 4 individually shielded Pairs laid up together & made circular
Inner Jacket
Material Nom. Diameter
LSZH – Low Smoke Zero Halogen (Flame Retardant) 12.7 mm (0.500 in)
Outer Shield
Shield Type Material Coverage Drainwire Type Notes
Braid Tinned Copper (TC) 60% 26 AWG (Solid) TC A Fire Protection Barrier: Mica Glass Tape & Water Blocking Tape wrapped over shielding
Armor
Armor Type & Material
SWB – Steel Wire Braid Armor
Outer Jacket
Material
LSZH – Low Smoke Zero Halogen (Flame Retardant)
Overall Cable Diameter (Nominal): 15.90 mm (0.6260 in)

Electrical Characteristics

Electricals
Max. Conductor DCR Nom. Characteristic Impedance
73.2 Ohm/km @ 20 Deg. C 100 Ohm
Delay
Max. Delay Skew
45 ns/100m
536 ns/100m
High Frequency
Frequency [MHz] Max. Insertion Loss (Attenuation) Min. NEXT [dB] Min. PSNEXT [dB] Min. RL (Return Loss) [dB]
4 3.8 dB/70m 66.3 63.3 23
8 5.4 dB/70m 61.8 58.8 24.5
10 6.0 dB/70m 60.3 57.3 25
16 7.6 dB/70m 57.2 54.2 25
20 8.5 dB/70m 55.8 52.8 25
25 9.6 dB/70m 54.3 51.3 24.3
31.25 10.7 dB/70m 52.9 49.9 23.6
62.5 15.5 dB/70m 48.4 45.4 21.5
100 19.9 dB/70m 45.3 42.3 20.1
200 29.1 dB/70m 40.8 37.8 18
250 33 dB/70m 39.3 36.3 17.3
300 36.6 dB/70m 38.1 35.1 17.3
400 43.2 dB/70m 36.3 33.3 17.3
500 49.2 dB/70m 34.8 31.8 17.3
Voltage
Voltage Rating
60 V

Mechanical Characteristics

Temperature
Operating
-40°C to + 80°C

Standards and Compliance

Environmental Suitability: UV Resistance, Oil Resistance
Flammability / Reaction to Fire: IEC 60332-1-2, IEC 60332-3-22, IEC 60331-23, BS EN 50200 PH120
Data Category: Category 6A
ISO/IEC Compliance: IEC 61034-2 – Smoke Density Min Transmittance = 60%
European Halogen Free Standards: IEC 60754-1 – Halogen Amount = 0.5 %, IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity = 10 µS/mm, IEC 60754-2 – Halogen Acid Gas Amount – Min. pH = 4.3
Other Standard Compliance(s): BS EN 50289-4-16

Product Notes

Notes: • TIA 568 D .2 Cat.5E and ISO/IEC 11801 class D and IEEE 802.3 100Base TX,1000Base T, Circuit integrity performance during a fire of the relevant requirements of IEC 60331 23.
• Cable will meet CAT 5e channel requirements up to 80m length or up to 70m permanent length.

History

Update and Revision: Revision Number: 0.17 Revision Date: 01-25-2024