C5762 – Teck90 1000V, 4+G C #10+12 Str BC, XLPE Ins M4, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Call for Price

Compare

Description

Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 4 10 AWG 7×18 BC – Bare Copper
Ground Wire 1 12 AWG 7×20 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) XLP, XLPO, XLPE (Thermoset) 0.045 in (1.1 mm) 0.204 in mm Red, Black, Blue, White
Ground Wire No Insulation
Outer Shield
Material
No Shield
Inner Jacket
Material Nom. Thickness Nom. Diameter
PVC – Polyvinyl Chloride 0.063 in (1.6 mm) 0.618 in (15.7 mm)
Armor
Armor Type & Material Diameter Over Armor
AIA – Aluminum Interlock Armor 0.843 in (21.4 mm)
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.048 in (1.2 mm) 0.939 in Yes
Overall Cable Diameter (Nominal): 0.939 in

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Max. Current
Conductor(s) 1.06 Ohm/1000ft 24 Amps per Conductor at 30ºC
Ground Wire 1.68 Ohm/1000ft (5.51 Ohm/km)
Voltage
Voltage Rating
1000 V (TECK 90)

Mechanical Characteristics

Temperature
Operating Installation
-40°C To +90°C -25°C To +90°C
Bend Radius
Stationary Min. Installation Min.
7.51 in (191 mm) 7.51 in
Max. Pull Tension: 864 lbs (392 kg)
Bulk Cable Weight: 433 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Burial
CEC / C(UL) Compliance: TECK 90, HL
European Directive Compliance: EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.230 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Putup Type UPC
C5762 01010000 Reel 612825284581
C5762 0102500 Reel 612825284604
C5762 0105000 Reel 612825284611
C5762 0107500 Reel 612825284642