A041A4B – TC VN/PVC, 4+G C #1+6 Str BC, PVC-NYL Ins M4, Blk PVC Jkt, 600V TC-ER 90C Dry 75C Wet SUN RES DIR BUR

Call for Price

Compare

Description

Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 4 1/0 AWG 19×12 BC – Bare Copper
Ground Wire 1 6 AWG 7×14 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC/Nylon – Polyvinyl Chloride + Nylon 0.057 in (1.4 mm) 0.485 in (12.3 mm) Black and Numbered
Ground Wire No Insulation
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.083 in (2.1 mm) 1.337 in Yes
Overall Cable Diameter (Nominal): 1.337 in

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Max. Current
Conductor(s) 0.10 Ohm/1000ft 136 Amps per Conductor at 30ºC
Ground Wire 0.42 Ohm/1000ft (1.4 Ohm/km) 75 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet -30°C To +90°C Wet/90°C Dry
Bend Radius
Stationary Min. Installation Min.
6.68 in (170 mm) 6.68 in
Max. Pull Tension: 5296 lbs (2402 kg)
Bulk Cable Weight: 1803 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to Fire: UL 1685 UL Loading, IEEE 1202 FT4
NEC / UL Compliance: Article 310, Article 336, TC-ER, THWN-2
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.55 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Putup Type
A041A4B 0102500 Reel