A0416KR – TC VN/PVC, 4 C #16 Str BC, PVC-NYL Ins E2, OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

Call for Price

Compare

Description

Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 4 16 AWG 7×24 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC/Nylon – Polyvinyl Chloride + Nylon 0.022 in (0.56 mm) 0.101 in mm Black, Red, Blue, Orange
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 18 AWG (7×26) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.047 in (1.2 mm) 0.342 in Yes
Overall Cable Diameter (Nominal): 0.342 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Max. Current
4.18 Ohm/1000ft 14.4 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet -25°C To +90°C
Bend Radius
Stationary Min. Installation Min.
4.104 in (104.2 mm) 4.104 in
Max. Pull Tension: 140 lbs (64 kg)
Bulk Cable Weight: 77 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to Fire: UL1685 UL Loading, FT4, IEEE 1202 FT4
NEC / UL Compliance: Article 336, TC-ER, TFFN
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
Plenum Number: ICEA S-73-532, S-95-658, S-61-402

History

Update and Revision: Revision Number: 0.47 Revision Date: 06-07-2023

Part Numbers

Variants
Item # Putup Type
A0416KR01020000 Reel