Description
Product Overview
Suitable Applications: | Power and Control Applications up to 600V |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 3 | 2/0 AWG | 19×11 | BC – Bare Copper |
Ground Wire | 1 | 6 AWG | 7×14 | BC – Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PVC/Nylon – Polyvinyl Chloride + Nylon | 0.062 in (1.6 mm) | 0.526 in mm | Black and Numbered |
Ground Wire | No Insulation |
Outer Shield
Material |
---|
No Shield |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.085 in (2.2 mm) | 1.301 in | Yes |
Overall Cable Diameter (Nominal): | 1.301 in |
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Max. Current |
---|---|---|
Conductor(s) | 0.084 Ohm/1000ft | 195 Amps per Conductor at 30ºC |
Ground Wire | 0.41 Ohm/1000ft (1.3 Ohm/km) | 120 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC-ER) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
90°C Dry, 90°C Wet | -30°C to 90°C Dry/Wet |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
6.505 in (165.2 mm) | 7.806 in |
Max. Pull Tension: | 5195.5 lbs (2356.6 kg) |
Bulk Cable Weight: | 167lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, Burial |
Flammability / Reaction to Fire: | UL 1685 UL Loading, IEEE 1202 FT4 |
NEC / UL Compliance: | Article 336, TC-ER, THWN-2 |
European Directive Compliance: | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
History
Update and Revision: | Revision Number: 0.66 Revision Date: 12-22-2023 |