A03182R – TC VN/PVC, 3 C #18 Str BC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Call for Price

Compare

Description

Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 3 18 AWG 7×26 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC/Nylon – Polyvinyl Chloride + Nylon 0.022 in (0.56 mm) 0.088 in mm Black, Red, Blue
Outer Shield
Material
No Shield
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.047 in (1.2 mm) 0.284 in Yes
Overall Cable Diameter (Nominal): 0.284 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Max. Current
6.7 Ohm/1000ft 14 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V (TC-ER), 150 V RMS (NPLF) (NPLF)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet -30°C to 90°C Dry/Wet
Bend Radius
Stationary Min. Installation Min.
1.136 in (28.85 mm) 1.42 in
Max. Pull Tension: 68 lbs (31 kg)
Bulk Cable Weight: 57 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Burial
Sustainability: CA Prop 65
Flammability / Reaction to Fire: UL 1685 UL Loading, IEEE 1202 FT4
NEC / UL Compliance: Article 336, TC-ER, TFFN
CEC / C(UL) Compliance: FT4
IEEE Compliance: 1202
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.126 Revision Date: 06-07-2023

Part Numbers

Variants
Item # Putup Type
A03182R01010000 Reel
A03182R01015000 Reel