Product Overview
Suitable Applications: |
low voltage analog signals (4-20ma, 0-10v, …); low voltage digital control (24v,
); line level audio; computer communication; panel wiring |
Physical Characteristics (Overall)
AWG |
Stranding |
Material |
No. of Pairs |
22 |
7×30 |
TC – Tinned Copper |
6 |
Material |
Nominal Diameter |
Diameter +/- Tolerance |
LSZH – Low Smoke Zero Halogen (Flame Retardant) |
1.27 mm |
0.05 mm |
Number |
Color |
Pair 1 |
Black & Red |
Pair 2 |
Black & White |
Pair 3 |
Black & Green |
Pair 4 |
Black & Blue |
Pair 5 |
Black & Yellow |
Pair 6 |
Black & Brown |
Table Notes: |
Shielded pairs |
Number |
Color |
Pair 1 |
Red |
Pair 2 |
Green |
Pair 3 |
Blue |
Pair 4 |
Blue |
Pair 5 |
Blue |
Pair 6 |
Blue |
Type |
Layer |
Material |
Material Trade Name |
Thickness of Foil |
Drainwire Material |
Drainwire AWG |
Tape |
1 |
Bi-Laminate (Alum+Poly) |
Beldfoil® (Z-Fold®) |
9 / 12 µm |
TC – Tinned Copper |
AWG22/7 |
Tape |
2 |
Polyester |
|
12 µm |
|
|
Material |
Bi-Laminate (Alum+Poly) |
Material |
Nominal Diameter |
Nominal Wall Thickness |
LSZH – Low Smoke Zero Halogen (Flame Retardant) |
10.1 mm |
1.3 mm |
Construction and Dimensions
Description |
Filler |
1 center filler and 6 pairs twisted to cable core covered with a polypropylene foil |
FRNC |
Electrical Characteristics
Nominal Conductor DCR |
Nominal Inner Shield DCR |
49.2 Ohm/km |
34.8 Ohm/km |
Nom. Capacitance Conductor to Conductor |
Nom. Capacitance Conductor to Other Conductor to Shield |
98.4 pF/m |
180.4 pF/m |
Nominal Pair Inductance |
0.59 µH/m |
Nominal Characteristic Impedance |
50 Ohm |
Element |
Max. Recommended Current [A] |
Conductor(s) |
2 A |
Temperature Range
Installation Temperature Range: |
-15°C To +70°C |
Storage Temperature Range: |
-30°C To +70°C |
Operating Temp Range (Flexible Install): |
-20°C To +70°C |
Operating Temp Range (Fixed Install): |
-30°C To +70°C |
Mechanical Characteristics
Min. Bend Radius During Installation: |
101 mm |
Standards
CPR Euroclass: |
Cca-s1,d1,a1 |
CENELEC Compliance: |
EN 50290-2-20 |
Applicable Environmental and Other Programs
Environmental Space: |
Indoor – Euroclass Cca |
Suitability
Suitability – Indoor: |
Yes |
Suitability – Non-Halogenated: |
Yes |
Suitability – Sunlight Resistance: |
Yes |
Flammability, LS0H, Toxicity Testing
IEC Flammability: |
IEC 60332-1-2 |
IEC 60754-1 – Halogen Amount: |
Zero |
IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity: |
2.5 µS/mm |
IEC 60754-2 – Halogen Acid Gas Amount – Min. pH: |
4.3 |
IEC 61034-2 – Smoke Density Min. Transmittance: |
60% |
History
Update and Revision: |
Revision Number: 0.20 Revision Date: 03-21-2024 |