8763 – Audio, Control and Instrumentation, 1 Pair 20 AWG, Shielded; 1 Conductor 20 AWG Unshielded

Call for Price

Compare

Description

Product Overview

Suitable Applications: low voltage analog signals (4-20ma, 0-10v, …); low voltage digital control (24v, …); line level audio; computer communication; panel wiring

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Pair(s) 1 20 AWG 7×28 TC – Tinned Copper
Conductor(s) 1 20 AWG 7×28 TC – Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Pair(s) PE – Polyethylene 0.014 in (0.36 mm) 0.066 in (1.7 mm) Shielded: Black & Red
Conductor(s) PE – Polyethylene 0.014 in (0.36 mm) 0.066 in (1.7 mm) Unshielded: Clear
Inner Shield
Element Shield Type Material Coverage Drainwire Type
Pair(s) Tape Bi-Laminate (Alum+Poly) 100% 20 AWG (7×28) TC
Conductor(s) No Shield
Outer Shield
Material
No Shield
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVC – Polyvinyl Chloride 0.0275 in (0.699 mm) 0.21 in
Overall Cable Diameter (Nominal): 0.21 in.

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Nom. Inner Shield DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Max. Current
Pair(s) 9.1 Ohm/1000ft 26 pF/ft (85 pF/m) 48 pF/ft (160 pF/m) 62 Ohm 3.9 Amps per Conductor at 25ºC
Conductor(s) 9.1 Ohm/1000ft (30 Ohm/km) 7.52 Ohm/1000ft (24.7 Ohm/km) 3.9 Amps per Conductor at 25ºC
Voltage
Voltage Rating
350 V

Mechanical Characteristics

Temperature
Operating
-30°C To +90°C
Bend Radius
Stationary Min. Installation Min.
2.1 in (53 mm) 2.1 in
Max. Pull Tension: 50 lbs (23 kg)
Bulk Cable Weight: 25 lbs/1000ft

Standards and Compliance

Environmental Suitability: Sunlight Resistance
CPR Compliance: CPR Euroclass: Eca
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation Compliance: UKCA Mark
APAC Compliance: China RoHS II (GB/T 26572-2011)

Product Notes

Notes: Beldfoil shield is over Red and Black pair only. Clear conductor is unshielded.

History

Update and Revision: Revision Number: 0.358 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Color Putup Type Length UPC Footnote
8763 0601000 Chrome Reel 1,000 ft 612825216193 C