Product Overview
Suitable Applications: |
low voltage analog signals (4-20ma, 0-10v, …); low voltage digital control (24v,
); line level audio; computer communication; panel wiring |
Physical Characteristics (Overall)
AWG |
Stranding |
Material |
No. of Pairs |
18 |
16×30 |
TC – Tinned Copper |
1 |
Material |
Nominal Diameter |
Diameter +/- Tolerance |
PE – Polyethylene |
2.08 mm |
0.05 mm |
Number |
Color |
Pair 1 |
Black & Clear |
Type |
Material |
Material Trade Name |
Coverage [%] |
Drainwire Material |
Drainwire AWG |
Drainwire Construction n x D |
Tape |
Bi-Laminate (Alum+Poly) |
Beldfoil® |
100% |
TC – Tinned Copper |
20 |
7×28 |
Material |
Color |
Nominal Diameter |
Nominal Wall Thickness |
LSZH – Low Smoke Zero Halogen (Flame Retardant) |
Chrome (RAL 7037) |
6.0 mm |
0.89 mm |
Electrical Characteristics
Nominal Conductor DCR |
21.3 Ohm/km |
Nom. Capacitance Conductor to Conductor |
Nom. Capacitance Conductor to Other Conductor to Shield |
98 pF/m |
144 pF/m |
Nominal Inductance |
0.591 µH/m |
Element |
Max. Recommended Current [A] |
Conductor(s) |
5.2 Amps per Conductor at 25ºC |
Temperature Range
Operating Temp Range (Flexible Install): |
-15°C To +80°C |
Operating Temp Range (Fixed Install): |
-45°C To +80°C |
Mechanical Characteristics
Oil Resistance: |
IEC 60811-404 |
Min. Bend Radius/Minor Axis: |
60 mm |
Standards
CPR Euroclass: |
Cca-s1,d1,a1 |
CENELEC Compliance: |
EN 50290-2-20 |
Applicable Environmental and Other Programs
Environmental Space: |
Indoor – Euroclass Cca |
EU Directive 2000/53/EC (ELV): |
Yes |
EU Directive 2003/96/EC (BFR): |
Yes |
EU Directive 2011/65/EU (RoHS 2): |
Yes |
EU Directive 2012/19/EU (WEEE): |
Yes |
Suitability
Suitability – Indoor: |
Yes |
Suitability – Non-Halogenated: |
Yes |
Suitability – Sunlight Resistance: |
Yes |
Flammability, LS0H, Toxicity Testing
IEC Flammability: |
IEC 60332-1-2 |
IEC 60754-1 – Halogen Amount: |
Zero |
IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity: |
2.5 µS/mm |
IEC 60754-2 – Halogen Acid Gas Amount – Min. pH: |
4.3 |
IEC 61034-2 – Smoke Density Min. Transmittance: |
60% |
Plenum/Non-Plenum
Related Part Numbers
Footnote: |
C – CRATE REEL PUT-UP. |
History
Update and Revision: |