7895A – DeviceBus®, 2 Pr #18+20 Str TC, PVC+FPE Ins, IS+OA TC Brd, PVC Jkt, CMG, PLTC

Call for Price

Compare

Description

Product Overview

Suitable Applications: harsh environment, ODVA device-level communication, used with CIP (common Industrial Protocol) for control, configuration, and data collection between devices, such as sensors and actuators, and higher level devices such as PLC, and PC in industrial automation, bus topology, etc.

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Power Pair(s) 1 18 AWG 19×30 TC – Tinned Copper
Data Pair(s) 1 20 AWG 19×32 TC – Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Power Pair(s) PVC – Polyvinyl Chloride 0.018 in (0.46 mm) 0.080 in (2.0 mm) Red & Black
Data Pair(s) PE – Polyethylene (Foam) 0.040 in (1.0 mm) 0.129 in (3.28 mm) Blue & White
Inner Shield
Element Shield Type Material Coverage
Power Pair(s) Tape Bi-Laminate (Alum+Poly) 100%
Data Pair(s) Tape Bi-Laminate (Alum+Poly) 100%
Outer Shield
Shield Type Material Coverage Drainwire Type
Braid Tinned Copper (TC) 65% 20 AWG (19×32) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVC – Polyvinyl Chloride 0.045 in (1.1 mm) 0.378 in (9.60 mm)
Table Notes: Jacket OD +/- 0.010
Overall Cable Diameter (Nominal): 0.378 in (9.60 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Max. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Power Pair(s) 6.9 Ohm/1000ft 6.9 Ohm/1000ft 4 Amps Per Conductor at 24 V (per NEC CL2) (Power Pair)
Data Pair(s) 10.9 Ohm/1000ft (35.8 Ohm/km) 10.9 Ohm/100m 12 pF/ft (39 pF/m) 120 Ohm 75%
Nom. Outer Shield DCR: 3.2 Ohm/1000ft (10 Ohm/km)
High Frequency
Element Frequency [MHz] Max. Insertion Loss (Attenuation)
Data Pair(s) 0.125 .29 dB/100ft
0.5 0.5 dB/100ft
1 0.7 dB/100ft
Voltage
UL Voltage Rating
300 V (CMG, PLTC), 600 V (UL AWM 20201)

Mechanical Characteristics

Temperature
UL Temperature Operating
75°C -20°C to +75°C
Bend Radius
Stationary Min. Installation Min.
3.8 in (97 mm) 3.8 in (97 mm)
Max. Pull Tension: 65 lbs (29 kg)
Bulk Cable Weight: 76 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Oil Resistance
Flammability / Reaction to Fire: UL 1685 FT4 Loading, FT4, IEEE 1202, IEC 60332-1-2
CPR Compliance: CPR Euroclass: Eca
NEC / UL Compliance: Article 725, Article 800, CMG, PLTC
AWM Compliance: AWM 20201
CEC / C(UL) Compliance: CMG
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation Compliance: UKCA Mark
Other Standard Compliance(s): ODVA Cable III

Product Notes

Notes: Mid. Meter marks on jacket to aid users in installation. ODVA DeviceNet is an Open DeviceNet Vendor Association, Inc. trademark.

History

Update and Revision: Revision Number: 0.546 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Color Putup Type Length UPC Footnote
7895A T5U500 Gray T5U Reel 500 ft 612825190806
7895A T5U1000 Gray T5U Reel 1,000 ft 612825190790 C
7895A T5U5000 Gray T5U Reel 5,000 ft 612825190813 C Z