Product Overview
Suitable Applications: |
Profibus PA or Foundation FieldBus PA |
Physical Characteristics (Overall)
AWG |
Stranding |
Material |
No. of Pairs |
18 |
7×26 |
TC – Tinned Copper |
1 |
Material |
Nominal Diameter |
Diameter +/- Tolerance |
PE – Polyethylene |
2.55 mm |
0.05 mm |
Number |
Color |
Wire 1 |
Red |
Wire 2 |
Green |
Type |
Material |
Drainwire Material |
Drainwire AWG |
Tape |
Bi-Laminate (Alum+Poly) |
TC – Tinned Copper |
20 |
Material |
Nominal Diameter |
PVC – Polyvinyl Chloride |
7.5 mm |
Construction and Dimensions
Description |
1 pair + tinned copper drainwire |
Electrical Characteristics
Max. Conductor DCR |
Max. Shield DCR |
20.5 Ohm/km |
26 Ohm/km |
Max. Capacitance Conductor to Conductor |
80 pF/m |
Frequency [MHz] |
Nominal Characteristic Impedance |
Nominal Characteristic Tolerance |
0.03125 MHz MHz |
100 Ohm |
20 Ohm |
Nominal Velocity of Propagation (VP) [%] |
66% |
Frequency [MHz] |
Max. Insertion Loss (Attenuation) |
0.01 MHz |
0.2 dB/100m |
0.039 MHz |
0.3 dB/100m |
0.1 MHz |
0.6 dB/100m |
0.5 MHz |
2.8 dB/100m |
1 MHz |
3.7 dB/100m |
Temperature Range
Installation Temperature Range: |
-5°C To +80°C |
Storage Temperature Range: |
-30°C To +80°C |
Operating Temperature Range: |
-30°C To +80°C |
Mechanical Characteristics
Min Bend Radius (W/o Pulling Strength): |
100 mm |
Standards
UL AWM Style Compliance: |
AWM 2464 |
Applicable Environmental and Other Programs
Environmental Space: |
Indoor |
Flammability, LS0H, Toxicity Testing
IEC Flammability: |
IEC 60332-1-2 |
Related Part Numbers
Item # |
Color |
Put-Up Type |
Length |
EAN |
70200E.00500 |
Black |
Reel |
500 m |
8719605012302 |
History
Update and Revision: |
Revision Number: 0.153 Revision Date: 02-15-2024 |