62P1402 – Inst PVC/PVC, 2 Pr #14 Str BC, PVC-NYL Ins E1, Blk PVC Jkt, TC-ER NPLF 90C Dry 75C Wet

Call for Price

Compare

Description

Product Overview

Suitable Applications: Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, …),low voltage digital control (24v, …), encoders, control circuits, distributed control

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Pair(s) 2 14 AWG 7×22 BC – Bare Copper
Insulation
Material Nom. Thickness Nom. Insulation Diameter Color Code
PVC/Nylon – Polyvinyl Chloride + Nylon 0.024 in (0.61 mm) 0.116 in (2.95 mm) ICEA Chart E1
Inner Shield
Element Shield Type Material Coverage Drainwire Type
Each Pair Tape Bi-Laminate (Alum+Poly) 100% 18 AWG (7×26) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVC – Polyvinyl Chloride 0.063 in (1.6 mm) 0.564 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Nom. Inner Shield DCR Max. Current
2.67 Ohm/1000ft 0.84 Ohm/1000ft (2.8 Ohm/km) 21 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 75°C Wet -30°C To +90°C Dry, +75°C Wet
Bend Radius
Stationary Min. Installation Min.
2.24 in (56.9 mm) 2.8 in
Max. Pull Tension: 263.2 lbs (119.4 kg)
Bulk Cable Weight: 146 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to Fire: UL 1685 UL loading, IEEE 1202 FT4
NEC / UL Compliance: Article 336, Article 760
European Directive Compliance: EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

History

Update and Revision: Revision Number: 0.51 Revision Date: 01-10-2024

Part Numbers

Variants
Item # Putup Type UPC
62P1402 0105000 Reel 612825363538
62P1402 0102540 Reel