61T1601 – Inst PVC/PVC, 1 Tri #16 Str BC, PVC-NYL Ins E1, OS, Blk PVC Jkt, TC-ER NPLF 90C Dry 75C Wet

Call for Price

Compare

Description

Product Overview

Suitable Applications: Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, …),low voltage digital control (24v, …), encoders, control circuits, distributed control

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 3 16 AWG 7×24 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC/Nylon – Polyvinyl Chloride + Nylon 0.022 in (0.56 mm) 0.101 in (2.57 mm) ICEA S-73-732 Table E1 (Triads: Black & White & Red and numbered)
Inner Shield
Material
No Shield
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 20 AWG (7×28) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.047 in (1.2 mm) 0.314 in Yes
Overall Cable Diameter (Nominal): 0.314 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Max. Current
4.2 Ohm/1000ft 18 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 75°C Wet -30°C To +90 °C Dry, +75°C Wet
Bend Radius
Stationary Min. Installation Min.
3.768 in (95.71 mm) 3.768 in
Max. Pull Tension: 119 lbs (54.0 kg)
Bulk Cable Weight: 60 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to Fire: UL1685 UL Loading, IEEE 1202 FT4
NEC / UL Compliance: Article 336, Article 760
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

Product Notes

Notes: Alternate color coding available upon request.

History

Update and Revision: Revision Number: 0.43 Revision Date: 01-10-2024