Description
Product Overview
Suitable Applications: | CEC Power and Control Applications |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 50 | 14 AWG | 7×22 | BC – Bare Copper |
Ground Wire | 1 | 14 AWG | 7×22 | BC – Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.030 in (0.76 mm) | 0.132 in (3.35 mm) | Black and Numbered |
Ground Wire | No Insulation |
Outer Shield
Material |
---|
No Shield |
Inner Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord | Color |
---|---|---|---|---|
PVC – Polyvinyl Chloride | 0.083 in (2.1 mm) | 1.276 in (32.41 mm) | Yes | Black |
Armor
Armor Type & Material | Armor Thickness | Diameter Over Armor |
---|---|---|
AIA – Aluminum Interlock Armor | 0.034 in (0.86 mm) | 1.536 in (39.01 mm) |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|---|---|
PVC – Polyvinyl Chloride | 0.053 in (1.3 mm) | 1.642 in (41.71 mm) |
Overall Cable Diameter (Nominal): | 1.642 in (41.71 mm) |
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Max. Current |
---|---|---|
Conductor(s) | 2.65 Ohm/1000ft | 12.5 Amps per Conductor at 30ºC |
Ground Wire | 2.67 Ohm/1000ft (8.76 Ohm/km) | 25 Amps per Conductor at 30ºC |
Voltage
Voltage Rating |
---|
600 V (TECK 90) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
90°C | -40°C To +90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
13.136 in (333.65 mm) | 13.136 in (333.65 mm) |
Max. Pull Tension: | 2984.6 lbs (1353.8 kg) |
Bulk Cable Weight: | 1471 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, UV Resistance |
CEC / C(UL) Compliance: | TECK 90, HL |
History
Update and Revision: | Revision Number: 0.62 Revision Date: 12-22-2023 |