6064 – Teck90 600V, 50+G C #14+14 Str BC, XLPE Ins M4, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Call for Price

Compare

Description

Product Overview

Suitable Applications: CEC Power and Control Applications

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 50 14 AWG 7×22 BC – Bare Copper
Ground Wire 1 14 AWG 7×22 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) XLP, XLPO, XLPE (Thermoset) 0.030 in (0.76 mm) 0.132 in (3.35 mm) Black and Numbered
Ground Wire No Insulation
Outer Shield
Material
No Shield
Inner Jacket
Material Nom. Thickness Nom. Diameter Ripcord Color
PVC – Polyvinyl Chloride 0.083 in (2.1 mm) 1.276 in (32.41 mm) Yes Black
Armor
Armor Type & Material Armor Thickness Diameter Over Armor
AIA – Aluminum Interlock Armor 0.034 in (0.86 mm) 1.536 in (39.01 mm)
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVC – Polyvinyl Chloride 0.053 in (1.3 mm) 1.642 in (41.71 mm)
Overall Cable Diameter (Nominal): 1.642 in (41.71 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Max. Current
Conductor(s) 2.65 Ohm/1000ft 12.5 Amps per Conductor at 30ºC
Ground Wire 2.67 Ohm/1000ft (8.76 Ohm/km) 25 Amps per Conductor at 30ºC
Voltage
Voltage Rating
600 V (TECK 90)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C -40°C To +90°C
Bend Radius
Stationary Min. Installation Min.
13.136 in (333.65 mm) 13.136 in (333.65 mm)
Max. Pull Tension: 2984.6 lbs (1353.8 kg)
Bulk Cable Weight: 1471 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, UV Resistance
CEC / C(UL) Compliance: TECK 90, HL

History

Update and Revision: Revision Number: 0.62 Revision Date: 12-22-2023