Description
Product Overview
Suitable Applications: | Monitor/Detection, Control Circuits, Initiating Circuits, Notification Circuits |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 4 | 18 AWG | 7×26 | TC – Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PP – Polypropylene | 0.008 in (0.20 mm) | 0.062 in (1.6 mm) | Black, Red, White, Green |
Outer Shield
Material |
---|
No Shield |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.017 in (0.43 mm) | 0.184 in | Yes |
Overall Cable Diameter (Nominal): | 0.184 in |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
---|---|---|
6.5 Ohm/1000ft | 22.0 pF/ft (72.2 pF/m) | 4 Amps per Conductor at 25ºC |
Voltage
UL Voltage Rating |
---|
300 V |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
75°C | 0°C To +75°C |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
1.84 in (46.7 mm) | 1.84 in |
Max. Pull Tension: | 89.6 lbs (40.6 kg) |
Bulk Cable Weight: | 28 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor – Riser, Indoor |
Flammability / Reaction to Fire: | UL1666 Riser, FT4 |
NEC / UL Compliance: | Article 800, CMR |
CEC / C(UL) Compliance: | CMG |
European Directive Compliance: | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
Plenum Number: | 6302UH |
History
Update and Revision: | Revision Number: 0.126 Revision Date: 12-20-2022 |
Part Numbers
Variants
Item # | Color | Putup Type | Length | UPC |
---|---|---|---|---|
5302UH 0081000 | Gray | Reel | 1,000 ft | 612825159636 |
5302UH 008U1000 | Gray | UnReel | 1,000 ft | 612825159711 |