Description
Product Overview
Suitable Applications: | Power and Control Applications up to 600V |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 12 | 12 AWG | 7×20 | BC – Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PVC/Nylon – Polyvinyl Chloride + Nylon | 0.019 in (0.48 mm) | 0.131 in (3.33 mm) | ICEA Chart E1 |
Outer Shield
Material |
---|
No Shield |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.063 in (1.6 mm) | 0.666 in | Yes |
Overall Cable Diameter (Nominal): | 0.666 in |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|---|
1.72 Ohm/1000ft | 15 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC-ER), 150 V (NPLF) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
90°C Dry, 90°C Wet | -30°C To +90°C Wet/90°C Dry |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
2.66 in (67.6 mm) | 3.33 in |
Max. Pull Tension: | 1041.6 lbs (472.46 kg) |
Bulk Cable Weight: | 371 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
Flammability / Reaction to Fire: | UL 1685 UL Loading, IEEE 1202 FT4 |
NEC / UL Compliance: | Article 310, Article 336, Article 760, TC-ER, NPLF, THWN-2 |
European Directive Compliance: | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
History
Update and Revision: | Revision Number: 0.54 Revision Date: 06-07-2023 |
Part Numbers
Variants
Item # | Putup Type | UPC |
---|---|---|
48119A 0102500 | Reel | |
48119A 0105000 | Reel | 612825378792 |