48119A – TC VN/PVC, 12 C #12 Str BC, PVC-NYL Ins E1, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Call for Price

Compare

Description

Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 12 12 AWG 7×20 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC/Nylon – Polyvinyl Chloride + Nylon 0.019 in (0.48 mm) 0.131 in (3.33 mm) ICEA Chart E1
Outer Shield
Material
No Shield
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.063 in (1.6 mm) 0.666 in Yes
Overall Cable Diameter (Nominal): 0.666 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Max. Current
1.72 Ohm/1000ft 15 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet -30°C To +90°C Wet/90°C Dry
Bend Radius
Stationary Min. Installation Min.
2.66 in (67.6 mm) 3.33 in
Max. Pull Tension: 1041.6 lbs (472.46 kg)
Bulk Cable Weight: 371 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to Fire: UL 1685 UL Loading, IEEE 1202 FT4
NEC / UL Compliance: Article 310, Article 336, Article 760, TC-ER, NPLF, THWN-2
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.54 Revision Date: 06-07-2023

Part Numbers

Variants
Item # Putup Type UPC
48119A 0102500 Reel
48119A 0105000 Reel 612825378792