Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 7 14 AWG 7×22 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC/Nylon – Polyvinyl Chloride + Nylon 0.024 in (0.61 mm) 0.116 in mm Black, White, Red, Green, Orange, Blue, White/Black
Outer Shield
Material
No Shield
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.047 in (1.2 mm) 0.442 in Yes
Overall Cable Diameter (Nominal): 0.442 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Max. Current
2.52 Ohm/1000ft 17.5 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet Wet/Dry: -30°C To +90°C
Bend Radius
Stationary Min. Installation Min.
1.768 in (44.91 mm) 2.21 in
Max. Pull Tension: 382.2 lbs (173.4 kg)
Bulk Cable Weight: 155 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to Fire: UL 1685 UL Loading, IEEE 1202 FT4
NEC / UL Compliance: Article 336, NPLF, TC-ER, THWN-2
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.57 Revision Date: 06-07-2023

Part Numbers

Variants
Item # Putup Type
48085A 010S5000 Reel