Description
Product Overview
Suitable Applications: | Power and Control Applications up to 600V |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 2 | 16 AWG | 7×24 | BC – Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PVC/Nylon – Polyvinyl Chloride + Nylon | 0.022 in (0.56 mm) | 0.101 in mm | Black, White |
Outer Shield
Material |
---|
No Shield |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.197 in x 0.298 in | Yes |
Overall Cable Diameter (Nominal): | 0.197 in x 0.298 in |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|---|
4.2 Ohm/1000ft | 18 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC), 150 V (NPLF) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
90°C Dry, 90°C Wet | Wet/Dry: -30°C To +90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
1.192 in (30.28 mm) | 1.49 in |
Max. Pull Tension: | 71.4 lbs (32.4 kg) |
Bulk Cable Weight: | 41 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
Flammability / Reaction to Fire: | UL 1685 UL Loading, IEEE 1202 FT4 |
NEC / UL Compliance: | Article 336, NPLF, TC |
European Directive Compliance: | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
History
Update and Revision: | Revision Number: 0.59 Revision Date: 02-15-2024 |
Part Numbers
Variants
Item # | Putup Type |
---|---|
47917A 0105000 | Reel |