38214 – UL Type PV Wire, #14 Str TC, XLPO Ins, PVC Jkt, 600V PV 90C Dry/Wet

Call for Price

Compare

Description

Product Overview

Suitable Applications: Interconnection wiring of grounded and ungrounded photovoltaic power systems as described in Section 690.31(A) of the 2008 NEC.

Physical Characteristics (Overall)

Conductor
AWG Stranding Material No. of Conductors
14 41×30 TC – Tinned Copper 1
Conductor Count: 1
Insulation
Material Nominal Wall Thickness
XLP, XLPO, XLPE (Thermoset) 0.048 in
XLP, XLPO, XLPE (Thermoset)
Outer Jacket
Material Nominal Diameter Nominal Wall Thickness
PVC – Polyvinyl Chloride 0.243 in 0.033 in

Electrical Characteristics

Conductor DCR
Nominal Conductor DCR
2.4 Ohm/1000ft
Current
Element Max. Recommended Current [A]
Single Conductor in Free Aair @ 30C Ambient 35 Amps Single Conductor in Free Air
Voltage
UL Voltage Rating
600 V

Temperature Range

UL Temp Rating: 90°C Wet/Dry
Operating Temperature Range: -40°C To +90°C

Mechanical Characteristics

Bulk Cable Weight: 36 lbs/1000ft
Max. Pull Tension: 53.5 lbs
Min. Bend Radius/Minor Axis: 2.4375 in

Standards

NEC/(UL) Compliance: PV, RHW-2, USE-2
UL AWM Style Compliance: N/A
Military Compliance: N/A

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV): Yes
EU Directive 2003/96/EC (BFR): Yes
EU Directive 2011/65/EU (RoHS 2): Yes
EU Directive 2012/19/EU (WEEE): Yes
EU Directive 2015/863/EU (RoHS 2 amendment): Yes
EU Directive Compliance: EU Directive 2003/11/EC (BFR)
MII Order #39 (China RoHS): Yes

Suitability

Suitability – Sunlight Resistance: Yes

Flammability, LS0H, Toxicity Testing

UL Flammability: VW-1
UL voltage rating: 600 V RMS

Plenum/Non-Plenum

Plenum (Y/N): No

Related Part Numbers

Variants
Item # Color Put-Up Type Length UPC
38214 0101000 Black Reel 1,000 ft 612825147657
38214 0105000 Black Reel 5,000 ft 612825147664
Footnote: C – CRATE REEL PUT-UP.

Product Notes

Notes: Separator material over conductor.

History