32P1802 – Inst PVC/PVC, 2 Pr #18 Str BC, PVC Ins E1, IS/OS, Blk PVC Jkt, 300V PLTC ITC CMG

Call for Price

Compare

Description

Product Overview

Suitable Applications: Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, …),low voltage digital control (24v, …),RTD, control circuits, distributed control system (DCS),programmable logic controller (PLC),  Solenoids, Valves, actuators, positioners

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Pair(s) 2 18 AWG 7×26 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Pair(s) PVC – Polyvinyl Chloride 0.017 in (0.43 mm) 0.080 in (2.0 mm) Black and White and Numbered
Inner Shield
Element Shield Type Material Coverage Drainwire Type
Pair(s) Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7×30) TC
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7×30) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.053 in (1.3 mm) 0.403 in Yes
Overall Cable Diameter (Nominal): 0.403 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Nom. Inner Shield DCR Max. Current
6.8 Ohm/1000ft 12.3 Ohm/1000ft (40.4 Ohm/km) 12 Amps per Conductor at 25ºC
Voltage
UL Voltage Rating
300 V

Mechanical Characteristics

Temperature
UL Temperature Operating
UL: 105°C, AWM 2464: 80°C -20°C to +105°C
Bend Radius
Stationary Min. Installation Min.
4.03 in (102 mm) 4.03 in
Max. Pull Tension: 117 lbs (53.1 kg)
Bulk Cable Weight: 73 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance
Flammability / Reaction to Fire: UL1685 FT4 Loading, FT4, IEEE 1202 FT4
NEC / UL Compliance: Article 725, Article 727, Article 800
AWM Compliance: AWM 2464
CEC / C(UL) Compliance: CMG

History

Update and Revision: Revision Number: 0.109 Revision Date: 01-10-2024

Part Numbers

Variants
Item # UPC
32P1802 0105000 612825359654