Description
Product Overview
Suitable Applications: | RS-485, POS; Computer communications; Low Voltage Analog Signals (4-20ma, 0-10v, …); Low Voltage Digital Control (24v, ); Line Level Audio; Panel Wiring; serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, etc. |
Construction Details
Conductor
Size | Stranding | Material |
---|---|---|
22 | 7×30 | TC – Tinned Copper |
Insulation
Material | Nom. Insulation Diameter | Color Code |
---|---|---|
PE – Polyethylene (Foam) | 2.04 mm (0.0803 in) | White/Blue & Blue/White, White/Orange & Orange/White |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 22 AWG (7×30) TC |
Braid | Tinned Copper (TC) | 65% |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|---|---|
LSZH – Low Smoke Zero Halogen (Flame Retardant) | 1.35 mm (0.0531 in) | 8.9 mm (0.35 in) |
Table Notes: | UV Stabilised |
Overall Cable Diameter (Nominal): | 8.9 mm (0.35 in) |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|---|---|---|---|---|
48.2 Ohm/km (14.7 Ohm/1000ft) | 36.1 pF/m (11.0 pF/ft) | 68.6 pF/m | 120 Ohm | 78% | 2.7 Amps per Conductor |
Nom. Outer Shield DCR: | 5.9 Ohm/km (1.8 Ohm/1000ft) |
High Frequency (Nominal/Typical)
Frequency [MHz] | Nom. Insertion Loss (Attenuation) |
---|---|
1 | 1.64 dB/100m |
Mechanical Characteristics
Temperature
Operating | Installation | Storage |
---|---|---|
-45°C To +80°C | -15°C To +80°C | -45°C To +80°C |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
45 mm (1.8 in) | 89 mm (3.5 in) |
Max. Pull Tension: | 290 N (65 lbf) |
Standards and Compliance
Environmental Suitability: | Indoor/Outdoor – Euroclass Eca, Non-Halogenated, Sunlight Resistance, Oil Resistance |
Flammability / Reaction to Fire: | IEC 60332-1-2 |
CPR Compliance: | CPR Euroclass: Eca; CPR UKCA Class: Eca |
ISO/IEC Compliance: | IEC 61034-2 – Smoke Density Min Transmittance = 60% |
CENELEC Compliance: | EN 50290-2-20 |
European Halogen Free Standards: | IEC 62821-1 Halogen Free Compliance = Yes, IEC 60754-1 – Halogen Amount = Zero, IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity = 2.5 µS/mm, IEC 60754-2 – Halogen Acid Gas Amount – Min. pH = 4.3 |
European Directive Compliance: | EU CE Mark |
UK Regulation Compliance: | UKCA Mark |
Other Standard Compliance(s): | DMX-512 |
History
Update and Revision: | Revision Number: 0.370 Revision Date: 12-22-2023 |
Part Numbers