3107ELS – RS-485, 2PR #22 Str TC, PO ins, F/B, LSNH Jkt, SWA

Call for Price

Compare

Description

Product Overview

Suitable Applications: Instrumentation and computer cable. For EIA RS-485 transmissions applications

Physical Characteristics (Overall)

Conductor
AWG Stranding Material No. of Pairs
22 7×30 TC – Tinned Copper 2
Conductor Count: 4
Total Number of Pairs: 2
Insulation
Material Nominal Diameter Diameter +/- Tolerance
PE – Polyethylene (Foam) 2.04 mm 0.05 mm
Color Chart
Number Color
Pair 1 White/Blue & Blue/White
Pair 2 White/Orange & Orange/White
Inner Shield
Material Material Trade Name Drainwire Material
Bi-Laminate (Alum+Poly) Beldfoil® TC – Tinned Copper
Inner Jacket
Nominal Diameter Nominal Wall Thickness
8.9 mm 1.35 mm
Table Notes: UV Stabilised
Outer Shield
Type Layer Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG
Tape 1 Beldfoil® 100% TC – Tinned Copper 22
Braid 2 Tinned Copper (TC) 65%
Outer Jacket
Material Color Nominal Diameter Nominal Wall Thickness
LSZH – Low Smoke Zero Halogen (Flame Retardant) Black 13.3 mm 1.35 mm

Construction and Dimensions

Armor
Type of Armor Material Thickness of Armoring Wires Coverage Percentage
Steel Wire Armoring Galvanized steel wire 0.9 mm Min. 90%

Electrical Characteristics

Conductor DCR
Nominal Conductor DCR Nominal Outer Shield DCR
48.2 Ohm/km 5.9 Ohm/km
Capacitance
Nom. Capacitance Conductor to Conductor Nom. Capacitance Conductor to Other Conductor to Shield
36.1 pF/m 68.6 pF/m
Impedance
Frequency [MHz] Nominal Characteristic Impedance
1 MHz 120 Ohm
High Frequency (Nominal/Typical)
Frequency [MHz] Nom. Insertion Loss
1 MHz 1.64 dB/100m
Delay
Nominal Velocity of Propagation (VP) [%]
78%
Current
Element Max. Recommended Current [A]
Conductor(s) 2.1 Amps per Conductor
Voltage
Voltage Rating [V]
300 V

Temperature Range

Installation Temperature Range: -15°C To +80°C
Storage Temperature Range: -45°C To +80°C
Operating Temperature Range: -15°C To +80°C
Operating Temp Range (Fixed Install): -45°C To +80°C

Mechanical Characteristics

Oil Resistance: IEC 60811-404
Max. Pull Tension: 290 N
Min Bend Radius (W/o Pulling Strength): 200 mm
Min. Bend Radius During Installation: 260 mm

Standards

CENELEC Compliance: EN 50290-2-20
Other Specification: DMX-512

Applicable Environmental and Other Programs

Environmental Space: Indoor, Indoor/Outdoor, Outdoor, Indoor/Outdoor – Euroclass Eca

Suitability

Suitability – Indoor: Yes
Suitability – Non-Halogenated: Yes
Suitability – Oil Resistance: Yes
Suitability – Outdoor: Yes
Suitability – Sunlight Resistance: Yes

Flammability, LS0H, Toxicity Testing

IEC Flammability: IEC 60332-1-2
IEC 60754-1 – Halogen Amount: Zero
IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity: 2.5 µS/mm
IEC 60754-2 – Halogen Acid Gas Amount – Min. pH: 4.3
IEC 61034-2 – Smoke Density Min. Transmittance: 60%

Related Part Numbers

Variants
Item # Color Put-Up Type Length EAN
3107ELS.00500 Black Reel 500 m
3107ELS.001000 Black Reel 1,000 m 8719605160508
3107ELS.001500 Black Reel 1,500 m 8719605195623

History