Description
Product Overview
Suitable Applications: | harsh environment, outdoors, data transmission applications such as Profibus DP or PA, Instrumentation and computer cable, etc. exposure to temperature extremes, humidity/moisture, dust, and oil. |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Pair(s) | 1 | 22 AWG | Solid | BC – Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code | Notes |
---|---|---|---|---|---|
Pair(s) | PE – Polyethylene (Foam) | 0.035 in (0.89 mm) | 0.099 in (2.5 mm) | Red & Green | Flame Retardant, Foam w/ skin |
Outer Shield
Shield Type | Material | Coverage |
---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% |
Braid | Tinned Copper (TC) | 65% |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|---|---|
PVC – Polyvinyl Chloride | 0.043 in (1.1 mm) | 0.315 in (8.00 mm) |
Table Notes: | Jacket OD +/- 0.010 |
Overall Cable Diameter (Nominal): | 0.315 in (8.00 mm) |
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|---|---|---|---|
Pair(s) | 18.9 Ohm/1000ft | 150 Ohm | 78% | 2.3 Amps per Conductor at 25ºC |
Nom. Outer Shield DCR: | 5.2 Ohm/1000ft (17 Ohm/km) |
High Frequency (Nominal/Typical)
Element | Frequency [MHz] | Nom. Insertion Loss (Attenuation) |
---|---|---|
Pair(s) | 0.2 | 0.27 dB/100ft |
4 | 0.67 dB/100ft | |
16 | 1.37 dB/100ft |
High Frequency
Frequency [MHz] | Max. Insertion Loss (Attenuation) |
---|---|
0.2 | 1.1 dB/100m |
4 | 2.65 dB/100m |
16 | 5.4 dB/100m |
Voltage
UL Voltage Rating |
---|
600 V (CMG, PLTC), 300 V (AWM 20201) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
75°C | -30°C to +75°C |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
2.4 in (61 mm) | 2.4 in (61 mm) |
Max. Pull Tension: | 50 lbs (23 kg) |
Bulk Cable Weight: | 52 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance |
Flammability / Reaction to Fire: | UL 1685 FT4 Loading, FT4, IEEE 1202, IEC 60332-1-2 |
CPR Compliance: | CPR Euroclass: Eca; CPR UKCA Class: Eca |
NEC / UL Compliance: | Article 725, Article 800, CM, CMX-Outdoor, PLTC, ITC |
AWM Compliance: | AWM 20201 |
CEC / C(UL) Compliance: | CMG |
European Directive Compliance: | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
UK Regulation Compliance: | UKCA Mark |
Product Notes
Notes: | Siemens Sinec L2 Cable. For CPE jacketed version order Part No. YR45047. For LSZH (FRNC) jacketed version, order Part No. 3079T or YR44731. |
History
Update and Revision: | Revision Number: 0.529 Revision Date: 02-15-2024 |
Part Numbers
Variants
Item # | Color | Putup Type | Length | UPC | Footnote |
---|---|---|---|---|---|
3079A 0601000 | Chrome | Reel | 1,000 ft | 612825140382 | C |
3079A 0602000 | Chrome | Reel | 2,000 ft | 612825140399 | C |
3079A 0071000 | Violet | Reel | 1,000 ft | 612825140344 | C |
3079A 0072000 | Violet | Reel | 2,000 ft | 612825140351 | C |
3079A 0075000 | Violet | Reel | 5,000 ft | 612825140375 |