3018A – Inst, 2 Tri #20 Str BC, PVC Ins E1, IS/OS, Blk PVC Jkt, 300V PLTC ITC CMG

Call for Price

Compare

Description

Product Overview

Suitable Applications: Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, …),low voltage digital control (24v, …),RTD, control circuits, distributed control system (DCS),programmable logic controller (PLC),  Solenoids, Valves, actuators, positioners

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Triad(s) 2 20 AWG 7×28 BC – Bare Copper
Comm Wire(s) 1 22 AWG 7×30 BC – Bare Copper
Insulation
Element Material Nom. Thickness Color Code
Triad(s) PVC – Polyvinyl Chloride 0.018 in (0.46 mm) Black, White, Red and Numbered
Comm Wire(s) Orange
Inner Shield
Element Shield Type Material Coverage Drainwire Type
Triad(s) Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7×30) TC
Comm Wire(s) No Shield
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 20 AWG (7×28) TC
Outer Jacket
Material Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.420 in (10.7 mm) Yes
Overall Cable Diameter (Nominal): 0.420 in (10.7 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR
Triad(s) 10.6 Ohm/1000ft (34.8 Ohm/km)
Comm Wire(s) 14.7 Ohm/1000ft (48.2 Ohm/km)
Voltage
UL Voltage Rating
300 V (CMG, PLTC, UL AWM 2464), 150 V (ITC)

Mechanical Characteristics

Temperature
UL Temperature Operating
105°C -30°C to +105°C
Bend Radius
Stationary Min. Installation Min.
4.2 in (110 mm) 4.2 in (110 mm)
Max. Pull Tension: 102 lbs (46.3 kg)
Bulk Cable Weight: 68 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor/Outdoor, Indoor, Outdoor, Sunlight Resistance
Flammability / Reaction to Fire: UL1685 (FT4 Loading), FT4, 1202
NEC / UL Compliance: Article 725, Article 727, Article 800, CMG, ITC, PLTC
CEC / C(UL) Compliance: CMG

History

Update and Revision: Revision Number: 0.56 Revision Date: 01-04-2024