Description
Product Overview
| Suitable Applications: | Variable Frequency Drives (VFD); AC Motor and Drive Systems; Human safety applications with flame or toxicity concerns (low smoke, zero halogen) |
Construction Details
Conductor
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Conductor(s) | 3 | 6 AWG | 7x19x27 | TC – Tinned Copper |
| Ground | 1 | 6 AWG | 7x19x27 | TC – Tinned Copper |
Insulation
| Element | Material | Nom. Thickness | Color Code |
|---|---|---|---|
| Conductor(s) | XLPE – Cross-Linked Polyethylene (Thermoset) | 0.062 in (1.6 mm) | Black and Numbered |
| Ground | PVC – Polyvinyl Chloride | 0.062 in (1.6 mm) | Green/Yellow Stripe |
Outer Shield
| Shield Type | Material | Coverage |
|---|---|---|
| Tape | Tri-Laminate (Alum+Poly+Alum) | 100% |
| Braid | Tinned Copper (TC) | 85% |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord |
|---|---|---|---|
| LSZH – Low Smoke Zero Halogen (Flame Retardant) | 0.095 in (2.4 mm) | 1.002 in (25.45 mm) | Yes |
| Overall Cable Diameter (Nominal): | 1.002 in (25.45 mm) |
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Nom. Inner Shield DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Shield | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
|---|---|---|---|---|---|---|---|---|
| Conductor(s) | 0.384 Ohm/1000ft (1.26 Ohm/km) | 4.99 Ohm/1000ft (16.4 Ohm/km) | 23 pF/ft (75 pF/m) | 42 pF/ft (140 pF/m) | 42 pF/ft (140 pF/m) | 80 Ohm | 55% | 24 Amps per Conductor at 30ºC |
Voltage
| UL Voltage Rating |
|---|
| 1000 V (TC, WTTC, UL Flexible Motor Supply Cable) |
Mechanical Characteristics
Temperature
| UL Temperature | Operating |
|---|---|
| 90°C Dry, 90°C Wet | -25°C To +90°C |
Bend Radius
| Stationary Min. | Installation Min. |
|---|---|
| 12.0 in (305 mm) | 12.0 in (305 mm) |
| Max. Pull Tension: | 1358 lbs (616.0 kg) |
| Bulk Cable Weight: | 782 lbs/1000ft (1160 kg/km) |
Standards and Compliance
| Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial |
| Sustainability: | CA Prop 65 |
| Flammability / Reaction to Fire: | UL1685 FT4 Loading |
| NEC / UL Compliance: | Article 336, TC-ER, WTTC, UL Flexible Motor Supply Cable |
| ICEA Compliance: | S-95-658 |
| APAC Compliance: | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision: | Revision Number: 0.259 Revision Date: 12-22-2023 |
Part Numbers
Variants
| Item # | Color | Putup Type | UPC |
|---|---|---|---|
| 29505T 0101000 | Black | Reel | 612825137191 |
| 29505T 0103500 | Black | Reel | 612825137207 |