28156AX – TC VN/PVC, 3 C #4 Str BC, PVC-NYL Ins M4, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet SUN RES DIR BUR

Call for Price

Compare

Description

Product Overview

Suitable Applications: Power and Control Applications up to 600V

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 3 4 AWG 7×12 BC – Bare Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Conductor(s) PVC/Nylon – Polyvinyl Chloride + Nylon 0.049 in (1.2 mm) 0.323 in mm Black and Numbered
Outer Shield
Material
No Shield
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.063 in (1.6 mm) 0.822 in Yes
Overall Cable Diameter (Nominal): 0.822 in

Electrical Characteristics

Electricals
Nom. Conductor DCR Max. Current
0.26 Ohm/1000ft 95 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
600 V

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet Wet/Dry: -30°C To +90°C
Bend Radius
Stationary Min. Installation Min.
3.288 in (83.52 mm) 4.11 in
Max. Pull Tension: 1659 lbs (752.5 kg)
Bulk Cable Weight: 547 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Sustainability: CA Prop 65
Flammability / Reaction to Fire: UL 1685 UL Loading, IEEE 1202 FT4
NEC / UL Compliance: Article 336, TC-ER, THWN-2
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.51 Revision Date: 06-07-2023

Part Numbers

Variants
Item # Putup Type
28156AX 0105000 Reel