Description
Product Overview
Suitable Applications: | Power and Control Applications up to 600V |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 5 | 10 AWG | 7×18 | BC – Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PVC/Nylon – Polyvinyl Chloride + Nylon | 0.024 in (0.61 mm) | 0.164 in (4.17 mm) | Black, Red, Blue, Orange, Yellow |
Outer Shield
Material |
---|
No Shield |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.063 in (1.6 mm) | 0.569 in (14.5 mm) | Yes |
Overall Cable Diameter (Nominal): | 0.569 in (14.5 mm) |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|---|
1.06 Ohm/1000ft | 32 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
90°C Dry, 90°C Wet | Wet/Dry: -30°C to 90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
2.276 in (57.81 mm) | 2.845 in (72.26 mm) |
Max. Pull Tension: | 740 lbs (340 kg) |
Bulk Cable Weight: | 257 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
Flammability / Reaction to Fire: | UL 1685 UL Loading, IEEE 1202 FT4 |
NEC / UL Compliance: | Article 336, Article 310, TC-ER, THWN-2 |
European Directive Compliance: | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
History
Update and Revision: | Revision Number: 0.391 Revision Date: 04-14-2023 |
Part Numbers
Variants
Item # | Color | Putup Type | Length | UPC |
---|---|---|---|---|
28141A 01020000 | Reel | |||
28141A 0105000 | Reel | 612825135463 | ||
28141A 0105000 | Reel | 612825135463 | ||
28141A 01010000 | Black | Reel | 10,000 ft | 612825135456 |