Description
Product Overview
Suitable Applications: | Power and Control Applications up to 600V |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 12 | 12 AWG | 7×20 | BC – Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PVC/Nylon – Polyvinyl Chloride + Nylon | 0.019 in (0.48 mm) | 0.131 in (3.33 mm) | Brown, Red, Orange, Yellow, Blue, Black |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 12 AWG (7×20) TC |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.063 in (1.6 mm) | 0.676 in (17.2 mm) | Yes |
Overall Cable Diameter (Nominal): | 0.676 in (17.2 mm) |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|---|
1.7 Ohm/1000ft | 15 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC-ER), 150 V (NPLF) |
Mechanical Characteristics
Temperature
UL Temperature |
---|
90°C Dry, 90°C Wet |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
8.112 in (206.0 mm) | 8.112 in (206.0 mm) |
Max. Pull Tension: | 1041.6 lbs (472.46 kg) |
Bulk Cable Weight: | 390 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
Flammability / Reaction to Fire: | UL 1685 UL Loading, IEEE 1202 FT4 |
NEC / UL Compliance: | Article 336, Article 310, TC-ER, THWN-2 |
History
Update and Revision: | Revision Number: 0.56 Revision Date: 04-14-2023 |