Description
Product Overview
Suitable Applications: | Power and Control Applications up to 600V |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 4 | 14 AWG | 7×22 | BC – Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PVC/Nylon – Polyvinyl Chloride + Nylon | 0.024 in (0.61 mm) | 0.116 in (2.95 mm) | Black, Red, Blue, Orange |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type |
---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 14 AWG (7×22) TC |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.377 in | Yes |
Overall Cable Diameter (Nominal): | 0.377 in |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|---|
2.67 Ohm/1000ft | 24 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC), 150 V (NPLF) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
90°C Dry, 75°C Wet | -30°C To +75°C Wet/90°C Dry |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
4.524 in (114.9 mm) | 4.524 in |
Max. Pull Tension: | 273 lbs (124 kg) |
Bulk Cable Weight: | 108 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, Burial |
Flammability / Reaction to Fire: | UL1685 UL Loading, IEEE 1202 FT4 |
NEC / UL Compliance: | Article 336, NPLF, TC, THHN, THWN |
European Directive Compliance: | EU CE Mark |
History
Update and Revision: | Revision Number: 0.374 Revision Date: 06-07-2023 |
Part Numbers
Variants
Item # | Color | Putup Type | Length | UPC | Footnote |
---|---|---|---|---|---|
27082AS 0105000 | Black | Reel | 5,000 ft | 612825132691 | C Z |
27082AS01010000 | Black | Reel | 10,000 ft | 612825132707 | C Z |