Product Overview
Suitable Applications: |
harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc. |
Physical Characteristics (Overall)
Element |
AWG |
Stranding |
Material |
No. of Pairs |
Pair(s) |
16 |
7×24 |
TC – Tinned Copper |
20 |
Total Number of Pairs: |
20 |
Material |
Nominal Wall Thickness |
XLPE – Cross-Linked Polyethylene (Thermoset) |
0.038 in |
Number |
Color |
1 |
Blue, Orange and Numbered |
2 |
|
3 |
|
4 |
|
5 |
|
6 |
|
7 |
|
8 |
|
9 |
|
10 |
|
11 |
|
12 |
|
13 |
|
14 |
|
15 |
|
16 |
|
17 |
|
18 |
|
19 |
|
20 |
|
Type |
Material |
Material Trade Name |
Coverage [%] |
Drainwire Material |
Drainwire AWG |
Tape |
Bi-Laminate (Alum+Poly) |
Beldfoil® |
100% |
TC – Tinned Copper |
18 |
Type |
Material |
Material Trade Name |
Coverage [%] |
Drainwire Material |
Drainwire AWG |
Tape |
Bi-Laminate (Alum+Poly) |
Beldfoil® |
100% |
TC – Tinned Copper |
16 |
Material |
Nominal Diameter |
Nominal Wall Thickness |
TPE – Thermoplastic Elastomer |
1.469 in |
0.085 in |
Electrical Characteristics
Nominal Conductor DCR |
4.2 Ohm/1000ft |
Nom. Capacitance Conductor to Conductor |
22 pF/ft |
Nominal Inductance |
0.22 µH/ft |
Nominal Characteristic Impedance |
100 Ohm |
High Frequency (Nominal/Typical)
Frequency [MHz] |
Nom. Insertion Loss |
0.039 MHz |
0.065 dB/100ft |
Nominal Velocity of Propagation (VP) [%] |
64% |
Max. Recommended Current [A] |
7.2 Amps per Conductor |
Electrical Characteristics Notes: |
Max Propagation Delay Change From 7.812 kHz to 39.06 kHz: 518 pS/ft |
Other Electrical Characteristic 2: |
31.25 KBits/sec |
Temperature Range
Operating Temperature Range: |
-40°C to 90°C |
Mechanical Characteristics
Bulk Cable Weight: |
1037 lbs/1000ft |
Max. Pull Tension: |
1911 lbs |
Min. Bend Radius/Minor Axis: |
14.75 in |
Standards
NEC Articles: |
Article 336 |
NEC/(UL) Compliance: |
TC-ER |
CSA AWM Compliance: |
AWM I A/B II A/B |
ISO/IEC Compliance: |
IEC 61158-2 |
Other Standards: |
ISA/SP-50 Type A |
Applicable Environmental and Other Programs
EU Directive 2000/53/EC (ELV): |
Yes |
EU Directive 2003/11/EC (BFR): |
Yes |
EU Directive 2011/65/EU (RoHS 2): |
Yes |
EU Directive 2012/19/EU (WEEE): |
Yes |
EU Directive 2015/863/EU (RoHS 2 amendment): |
Yes |
EU Directive Compliance: |
EU Directive 2003/11/EC (BFR) |
Suitability
Suitability – Burial: |
Yes |
Suitability – Indoor: |
Yes |
Suitability – Outdoor: |
Yes |
Suitability – Sunlight Resistance: |
Yes |
Flammability, LS0H, Toxicity Testing
UL Flammability: |
UL1581 Vertical Tray |
IEC Flammability: |
IEC 60332-3-24 |
UL voltage rating: |
600 V RMS |
Plenum/Non-Plenum
Related Part Numbers
Item # |
Color |
UPC |
2133A 0061000 |
Blue, Light |
612825130376 |
2133A 0031000 |
Orange |
612825130369 |
History
Update and Revision: |
Revision Number: 0.306 Revision Date: 12-22-2023 |