2130A – Fieldbus, 8 Pr #16 Str TC, XLPE Ins, IS/OS, TPE Jkt, 600V TC-ER

Call for Price

Compare

Description

Product Overview

Suitable Applications: harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Pair(s) 8 16 AWG 7×24 TC – Tinned Copper
Insulation
Element Material Nom. Thickness Color Code
Pair(s) XLPE – Cross-Linked Polyethylene (Thermoset) 0.038 in (0.97 mm) Blue, Orange and Numbered
Inner Shield
Element Shield Type Material Coverage Drainwire Type Notes
Pair(s) Tape Bi-Laminate (Alum+Poly) 100% 18 AWG (7×26) TC Individually Shielded
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 16 AWG (7×24) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
TPE – Thermoplastic Elastomer 0.085 in (2.2 mm) 0.982 in (24.9 mm) Yes
Overall Cable Diameter (Nominal): 0.982 in (24.9 mm)

Electrical Characteristics

Electricals
Nom. Conductor DCR Max. Capacitance Unbalance Nom. Capacitance Cond-to-Cond Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
4.2 Ohm/1000ft (14 Ohm/km) 1.2 pF/ft (3.9 pF/m) 22 pF/ft (72 pF/m) 100 Ohm 64% 10.1 Amps per Conductor
High Frequency (Nominal/Typical)
Nom. Insertion Loss (Attenuation)
0.065 dB/100ft
High Frequency
Max. Insertion Loss (Attenuation) Max./Min. Input Impedance (unFitted)
0.091 dB/100ft 100 Ohm
Voltage
UL Voltage Rating
600 V (TC-ER), 600 V (CSA CIC Type TC)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Wet/Dry -40°C to 90°C
Table Notes: -40C
Max. Pull Tension: 786 lbs (357 kg)
Bulk Cable Weight: 478 lbs/1000ft (711 kg/km)

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
Flammability / Reaction to Fire: UL1581 Vertical Tray, IEC 60332-3-24
NEC / UL Compliance: Article 336, TC-ER
AWM Compliance: AWM I A/B II A/B
CEC / C(UL) Compliance: CIC, TC
ISO/IEC Compliance: IEC 61158-2
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)
Other Standard Compliance(s): ISA/SP-50 Type A

History

Update and Revision: Revision Number: 0.457 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Color Putup Type Length UPC
2130A 0061000 Blue, Light Reel 1,000 ft 612825130178
2130A 0065000 Blue, Light Reel 5,000 ft 612825130185
2130A 0031000 Orange Reel 1,000 ft 612825130154
2130A 0035000 Orange Reel 5,000 ft 612825130161