Description
Product Overview
Suitable Applications: | harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc. |
Construction Details
Conductor
Element | Size | Stranding | Material |
---|---|---|---|
Pair(s) | 18 AWG | 7×26 | TC – Tinned Copper |
Insulation
Element | Material | Color Code | Notes |
---|---|---|---|
Conductor(s) | PP – Polypropylene | Blue & Orange | |
Ground | PP – Polypropylene | Green/Yellow | Flame Retardant |
Inner Shield
Element |
---|
Data Pair(s) |
Outer Shield
Material |
---|
Bi-Laminate (Alum+Poly) |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter |
---|---|---|
PVC – Polyvinyl Chloride | 0.060 in (1.5 mm) | 0.362 in (9.19 mm) |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Nom. Characteristic Impedence | Max. Current |
---|---|---|
7.06 Ohm/1000ft | 100 Ohm | 5 Amps per Conductor |
Nom. Outer Shield DCR: | 1.51 Ohm/1000ft (4.95 Ohm/km) |
Voltage
UL Voltage Rating |
---|
600 V |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
75°C | -30°C to +75°C |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
3.62 in (91.9 mm) | 3.62 in (91.9 mm) |
Max. Pull Tension: | 44.8 lbs (20.3 kg) |
Bulk Cable Weight: | 68 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Outdoor, Sunlight Resistance, UV Resistance, Oil Resistance |
Flammability / Reaction to Fire: | UL1685 UL Loading |
NEC / UL Compliance: | Article 725, TC-ER |
History
Update and Revision: | Revision Number: 0.413 Revision Date: 08-10-2023 |
Part Numbers
Variants
Item # | Color | UPC |
---|---|---|
1337A 00310000 | Orange | 612825112266 |