129842 – RS485, 2 Pr #24 Str TC, PE Ins, OS+TC Brd, PVC Jkt, AIA Armor, PVC Jkt, CM

Call for Price

Compare

Description

Product Overview

Suitable Applications: exposure to rodent, crush, or cut through force, burial, POS, serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, outdoor such as solar, lighting, etc.

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Pair(s) 2 24 AWG 7×32 TC – Tinned Copper
Insulation
Element Material Nom. Thickness Color Code
Pair(s) PE – Polyethylene 0.022 in (0.56 mm) White/Blue Stripe & Blue/White Stripe, White/Orange Stripe & Orange/White Stripe
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 24 AWG (7×32) TC
Braid Tinned Copper (TC) 90%
Inner Jacket
Material Nom. Diameter
PVC – Polyvinyl Chloride 0.340 in (8.64 mm)
Armor
Armor Type & Material
AIA – Aluminum Interlock Armor
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVC – Polyvinyl Chloride 0.045 in (1.1 mm) 0.620 in (15.7 mm)
Overall Cable Diameter (Nominal): 0.620 in (15.7 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Pair(s) 24 Ohm/1000ft (79 Ohm/km) 12.8 pF/ft (42.0 pF/m) 23 pF/ft 120 Ohm 66% 2.1 Amps per Conductor at 25ºC
Nom. Outer Shield DCR: 2.2 Ohm/1000ft (7.2 Ohm/km)
High Frequency (Nominal/Typical)
Element Frequency [MHz] Nom. Insertion Loss (Attenuation)
Pair(s) 1 0.6 dB/100ft
Voltage
UL Voltage Rating
300 V (CM)

Mechanical Characteristics

Temperature
UL Temperature Operating
80°C -30°C to +80°C
Table Notes: -40C CSA
Bend Radius
Stationary Min. Installation Min.
6.2 in (160 mm) 6.2 in
Max. Pull Tension: 200 lbs (91 kg)
Bulk Cable Weight: 162 lbs/1000ft (241 kg/km)

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance
Flammability / Reaction to Fire: IEC 60332-1-2
NEC / UL Compliance: Article 800, CM
CEC / C(UL) Compliance: CMG
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.312 Revision Date: 12-22-2023