TP12018W – Inst, 1 Pr #12 Str TC, XLPE Ins E1, Blk LSZH Jkt, 600V TC 90C Dry/Wet SUN RES

Call for Price

Compare

Description

Product Overview

Suitable Applications: Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, …),low voltage digital control (24v, …), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Physical Characteristics (Overall)

Conductor
AWG Stranding Material Nominal Diameter
12 7×20 TC – Tinned Copper 0.089 in
Conductor Count: 2
Total Number of Pairs: 1
Insulation
Material Nominal Diameter Nominal Wall Thickness
XLP, XLPO, XLPE (Thermoset) 0.150 in 0.030 in
Color Chart
Number Color
1 Black
2 White
Outer Jacket
Material Nominal Diameter Nominal Wall Thickness
LSZH – Low Smoke Zero Halogen (Flame Retardant) 0.384 in 0.047 in

Electrical Characteristics

Conductor DCR
Nominal Conductor DCR
1.65 Ohm/1000ft
Current
Max. Recommended Current [A]
31 Amps per Conductor at 30ºC

Temperature Range

UL Temp Rating: 90°C Wet/Dry
Operating Temperature Range: -25°C To +90°C

Mechanical Characteristics

Bulk Cable Weight: 87 lbs/1000ft
Max. Pull Tension: 173 lbs
Min Bend Radius (Overall): 4.0 in

Standards

NEC Articles: Article 336
NEC/(UL) Compliance: TC, XHHW-2

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV): Yes
EU Directive 2011/65/EU (RoHS 2): Yes
EU Directive 2012/19/EU (WEEE): Yes
EU Directive 2015/863/EU (RoHS 2 amendment): Yes
EU Directive Compliance: EU Directive 2003/11/EC (BFR)
EU CE Mark: Yes
CA Prop 65: Yes

Suitability

Suitability – Indoor: Yes
Suitability – Outdoor: Yes
Suitability – Sunlight Resistance: Yes

Flammability, LS0H, Toxicity Testing

CSA/C(UL) Flammability: FT4
UL voltage rating: 600 V RMS (Type TC)

History

Update and Revision: Revision Number: 0.39 Revision Date: 02-15-2024