Suitable Applications: | CEC Power and Control Applications up to 600V |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 3 | 2/0 AWG | 19×11 | BC – Bare Copper |
Ground Wire | 1 | 6 AWG | 7×14 | BC – Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.08 in (2.0 mm) | 0.571 in mm | Red, Black, Blue |
Ground Wire | No Insulation |
Outer Shield
Material |
---|
No Shield |
Inner Jacket
Material | Nom. Thickness | Nom. Diameter |
---|---|---|
PVC – Polyvinyl Chloride | 0.083 in (2.1 mm) | 1.394 in (35.41 mm) |
Armor
Armor Type & Material | Diameter Over Armor |
---|---|
AIA – Aluminum Interlock Armor | 1.654 in (42.01 mm) |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.053 in (1.3 mm) | 1.76 in (44.7 mm) | Yes |
Overall Cable Diameter (Nominal): | 1.76 in (44.7 mm) |
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Max. Current |
---|---|---|
Conductor(s) | 0.0827 Ohm/1000ft | 24 Amps per Conductor at 30ºC |
Ground Wire | 0.419 Ohm/1000ft (1.37 Ohm/km) |
Voltage
Voltage Rating |
---|
1000 V (TECK 90) |
Mechanical Characteristics
Temperature
Operating | Installation |
---|---|
-40°C To +90°C | -25°C To +90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
14.08 in (357.6 mm) | 14.08 in (357.6 mm) |
Max. Pull Tension: | 5395.5 lbs (2447.4 kg) |
Bulk Cable Weight: | 2199 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, Burial |
CEC / C(UL) Compliance: | TECK 90, HL |
European Directive Compliance: | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
APAC Compliance: | China RoHS II (GB/T 26572-2011) |
History
Update and Revision: | Revision Number: 0.249 Revision Date: 12-22-2023 |