Description
Product Overview
Suitable Applications: | Power and Control Applications up to 600V |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 2 | 12 AWG | 7×20 | BC – Bare Copper |
Ground Wire | 1 | 12 AWG | 7×20 | BC – Bare Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Conductor(s) | PVC/Nylon – Polyvinyl Chloride + Nylon | 0.021 in (0.53 mm) | 0.134 in mm | Black, White |
Ground Wire | PVC/Nylon – Polyvinyl Chloride + Nylon | 0.021 in (0.53 mm) | 0.134 in in | Green |
Outer Shield
Material |
---|
No Shield |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.383 in | Yes |
Overall Cable Diameter (Nominal): | 0.383 in |
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Max. Current |
---|---|---|
Conductor(s) | 1.68 Ohm/1000ft | 30 Amps per Conductor at 30ºC |
Ground Wire | 1.72 Ohm/1000ft (5.64 Ohm/km) |
Voltage
UL Voltage Rating |
---|
600 V |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
90°C Dry, 90°C Wet | -30°C to 90°C Wet/Dry |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
1.532 in (38.91 mm) | 1.915 in |
Max. Pull Tension: | 154 lbs (69.9 kg) |
Bulk Cable Weight: | 107 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
Flammability / Reaction to Fire: | UL 1685 UL Loading, IEEE 1202 FT4 |
NEC / UL Compliance: | TC-ER, THWN-2 |
European Directive Compliance: | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
History
Update and Revision: | Revision Number: 0.95 Revision Date: 12-22-2023 |