Welcome to American Tele Data

USA MADE - BABA COMPLIANT

AMERICAN TELEDATA

855 - 848 - Data

855 - 40 - Fiber

3107ENH – RS-485, 2 Pr #22 Str TC, PO ins, F/B, LSNH Jkt

Call for Price

Description

Product Overview

Suitable Applications: RS-485, POS; Computer communications; Low Voltage Analog Signals (4-20ma, 0-10v, …); Low Voltage Digital Control (24v, …); Line Level Audio; Panel Wiring; serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, etc.

Construction Details

Conductor
Size Stranding Material
22 7×30 TC – Tinned Copper
Insulation
Material Nom. Insulation Diameter Color Code
PE – Polyethylene (Foam) 2.04 mm (0.0803 in) White/Blue & Blue/White, White/Orange & Orange/White
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7×30) TC
Braid Tinned Copper (TC) 65%
Outer Jacket
Material Nom. Thickness Nom. Diameter
LSZH – Low Smoke Zero Halogen (Flame Retardant) 1.35 mm (0.0531 in) 8.9 mm (0.35 in)
Table Notes: UV Stabilised
Overall Cable Diameter (Nominal): 8.9 mm (0.35 in)

Electrical Characteristics

Electricals
Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
48.2 Ohm/km (14.7 Ohm/1000ft) 36.1 pF/m (11.0 pF/ft) 68.6 pF/m 120 Ohm 78% 2.7 Amps per Conductor
Nom. Outer Shield DCR: 5.9 Ohm/km (1.8 Ohm/1000ft)
High Frequency (Nominal/Typical)
Frequency [MHz] Nom. Insertion Loss (Attenuation)
1 1.64 dB/100m

Mechanical Characteristics

Temperature
Operating Installation Storage
-45°C To +80°C -15°C To +80°C -45°C To +80°C
Bend Radius
Stationary Min. Installation Min.
45 mm (1.8 in) 89 mm (3.5 in)
Max. Pull Tension: 290 N (65 lbf)

Standards and Compliance

Environmental Suitability: Indoor/Outdoor – Euroclass Eca, Non-Halogenated, Sunlight Resistance, Oil Resistance
Flammability / Reaction to Fire: IEC 60332-1-2
CPR Compliance: CPR Euroclass: Eca; CPR UKCA Class: Eca
ISO/IEC Compliance: IEC 61034-2 – Smoke Density Min Transmittance = 60%
CENELEC Compliance: EN 50290-2-20
European Halogen Free Standards: IEC 62821-1 Halogen Free Compliance = Yes, IEC 60754-1 – Halogen Amount = Zero, IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity = 2.5 µS/mm, IEC 60754-2 – Halogen Acid Gas Amount – Min. pH = 4.3
European Directive Compliance: EU CE Mark
UK Regulation Compliance: UKCA Mark
Other Standard Compliance(s): DMX-512

History

Update and Revision: Revision Number: 0.370 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Color Putup Type Length EAN
3107ENH.00305 Black Reel 305 m 8719605005977
3107ENH.K0305 Black Reel 305 m 8719605188755
3107ENH.001000 Black Reel 1,000 m 8719605174185
3107ENH.01500 Orange Reel 500 m 8719605192486