3030A – Inst, 4 Tri #18 Str BC, PVC Ins E1, OS, Blk PVC Jkt, 300V PLTC ITC CMG

Call for Price

Compare

Description

Product Overview

Suitable Applications: Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, …),low voltage digital control (24v, …),RTD, control circuits, distributed control system (DCS),programmable logic controller (PLC),  Solenoids, Valves, actuators, positioners

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Triad(s) 4 18 AWG 7×26 BC – Bare Copper
Comm Wire(s) 1 22 AWG 7×30 BC – Bare Copper
Insulation
Element Material Nom. Thickness Color Code
Triad(s) PVC – Polyvinyl Chloride 0.017 in (0.43 mm) Black, White, Red and Numbered
Comm Wire(s) PVC – Polyvinyl Chloride 0.019 in (0.48 mm) Orange
Inner Shield
Element Shield Type
Comm Wire(s) No Shield
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 18 AWG (7×26) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC – Polyvinyl Chloride 0.053 in (1.3 mm) 0.485 in (12.3 mm) Yes
Overall Cable Diameter (Nominal): 0.485 in (12.3 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR
Pair(s) 5.86 Ohm/1000ft (19.2 Ohm/km)
Comm Wire(s) 14.7 Ohm/1000ft (48.2 Ohm/km)
Voltage
UL Voltage Rating
300 V (CMG, PLTC, UL AWM 2464), 150 V (ITC)

Mechanical Characteristics

Temperature
UL Temperature Operating
105°C -30°C to +105°C
Bend Radius
Stationary Min. Installation Min.
4.9 in (120 mm) 4.9 in (120 mm)
Max. Pull Tension: 240 lbs (110 kg)
Bulk Cable Weight: 138 lbs/1000ft

Standards and Compliance

Environmental Suitability: Indoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to Fire: UL1685 (FT4 Loading), FT4, 1202
NEC / UL Compliance: Article 725, Article 727, Article 800, CMG, ITC, PLTC
AWM Compliance: AWM 2464
CEC / C(UL) Compliance: CMG

History

Update and Revision: Revision Number: 0.59 Revision Date: 01-04-2024