29503F – VFD 300% Gnd, 3C+G #10 Str TC, XLPE Ins+PVC Gnd, OS+TC Brd w/#10 TC Drain, Blk TPE Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC

Call for Price

Description

Product Overview

Suitable Applications: Variable Frequency Drives (VFD); AC Motor and Drive Systems, Exposure to high flex, motion, and abrasion, Hard to reach installation areas

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 3 10 AWG 7x37x34 TC – Tinned Copper
Ground 1 10 AWG 7x37x34 TC – Tinned Copper
Insulation
Element Material Nom. Thickness Color Code
Conductor(s) XLPE – Cross-Linked Polyethylene (Thermoset) 0.046 in (1.2 mm) Black and Numbered
Ground PVC – Polyvinyl Chloride 0.046 in (1.2 mm) Green/Yellow Stripe
Outer Shield
Shield Type Material Coverage
Tape Tri-Laminate (Alum+Poly+Alum) 100%
Braid Tinned Copper (TC) 85%
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
TPE – Thermoplastic Elastomer 0.073 in (1.9 mm) 0.716 in (18.2 mm) Yes
Overall Cable Diameter (Nominal): 0.716 in (18.2 mm)

Electrical Characteristics

Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Conductor(s) 1.003 Ohm/1000ft (3.291 Ohm/km) 45 pF/ft (150 pF/m) 81 pF/ft (270 pF/m) 41 Ohm 55% 40 Amps per Conductor at 30ºC (per NEC)
Voltage
UL Voltage Rating
1000 V (TC, WTTC, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC)

Mechanical Characteristics

Temperature
UL Temperature Operating
90°C Dry, 90°C Wet -40°C To +90°C
Bend Radius
Stationary Min. Installation Min. Flexing Min.
3.6 in (91 mm) 5.4 in (140 mm) 5.4 in (140 mm)
Max. Pull Tension: 666 lbs (302 kg)
Bulk Cable Weight: 357 lbs/1000ft (531 kg/km)

Standards and Compliance

Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
Sustainability: CA Prop 65
Flammability / Reaction to Fire: UL1685 UL Loading, FT4, 1202, 383 Vertical Tray Flame Test (70,000 BTU)
NEC / UL Compliance: Article 336, TC-ER, XHHW-2, RHW-2, UL Flexible Motor Supply Cable
CEC / C(UL) Compliance: CIC, TC
ICEA Compliance: S-95-658
European Directive Compliance: EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.189 Revision Date: 12-22-2023

Part Numbers

Variants
Item # Color Putup Type Length UPC
29503F 0101000 Black Reel 1,000 ft 612825367178
29503F 0105000 Black Reel 5,000 ft 612825367185