Description
Product Overview
Suitable Applications: | Power and Control Applications up to 600V |
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Conductor(s) | 4 | 10 | 7×18 | BC – Bare Copper |
Insulation
Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|
PVC/Nylon – Polyvinyl Chloride + Nylon | 0.022 in (0.56 mm) | 0.156 in (3.96 mm) | Black, Red, Blue, Orange |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC – Polyvinyl Chloride | 0.047 in (1.2 mm) | 0.495 in (12.6 mm) | Yes |
Electrical Characteristics
Electricals
Nom. Conductor DCR | Max. Current |
---|---|
1.06 Ohm/1000ft | 32 Amps per Conductor at 30ºC |
Voltage
UL Voltage Rating |
---|
600 V (TC-ER) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
90°C Dry, 90°C Wet | Wet/Dry: -30°C to 90°C |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
1.96 in (49.8 mm) | 2.45 in (62.2 mm) |
Max. Pull Tension: | 600 lbs (270 kg) |
Bulk Cable Weight: | 156 lbs/1000ft |
Standards and Compliance
Environmental Suitability: | Indoor, Outdoor, Sunlight Resistance, Burial |
Flammability / Reaction to Fire: | UL 1685 UL loading, IEEE 1202 FT4 |
NEC / UL Compliance: | Article 336, TC-ER, THWN-2 Singles |
European Directive Compliance: | EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
History
Update and Revision: | Revision Number: 0.549 Revision Date: 04-14-2023 |
Part Numbers
Variants
Item # | Color | Putup Type | Length | UPC | Footnote |
---|---|---|---|---|---|
28140A 0105000 | Black | Reel | 5,000 ft | 612825135449 | C Z |
28140A 01010000 | Black | Reel | 10,000 ft | 612825135432 | C Z |