123084F – DeviceBus®, 2 Pr #22+24 Str TC, PVC+FPE Ins, IS+OA TC Brd, PVC Jkt, AIA Armor, PVC Jkt, Flexible, CMG, CL2

Call for Price

Compare

Description

Product Overview

Suitable Applications: exposure to rodent, crush, or cut through force, harsh environment, ODVA device-level communication, used with CIP (common Industrial Protocol) for control, configuration, and data collection between devices, such as sensors and actuators, and higher level devices such as PLC, and PC in industrial automation, bus topology, etc.

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Power Pair(s) 1 22 AWG 154×44 TC – Tinned Copper
Data Pair(s) 1 24 AWG 105×44 TC – Tinned Copper
Insulation
Element Material Nom. Thickness Color Code
Power Pair(s) PVC – Polyvinyl Chloride 0.016 in (0.41 mm) Red & Black
Data Pair(s) PE – Polyethylene (Foam) 0.026 in (0.66 mm) Blue & White
Inner Shield
Element Shield Type Material Coverage
Power Pair(s) Tape Bi-Laminate (Alum+Poly) 100%
Data Pair(s) Tape Bi-Laminate (Alum+Poly) 100%
Outer Shield
Shield Type Material Coverage Drainwire Type
Braid Tinned Copper (TC) 65% 22 AWG (26×36) TC
Inner Jacket
Material Nom. Diameter
PVC – Polyvinyl Chloride 0.275 in (6.99 mm)
Armor
Armor Type & Material
AIA – Aluminum Interlock Armor
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVC – Polyvinyl Chloride 0.045 in (1.1 mm) 0.573 in (14.6 mm)
Overall Cable Diameter (Nominal): 0.573 in (14.6 mm)

Electrical Characteristics

Electricals
Element Nom. Characteristic Impedence Nom. Velocity of Prop.
Power Pair(s)
Data Pair(s) 120 Ohm 75%
High Frequency
Element
Data Pair(s)
Voltage
UL Voltage Rating
300 V (CMG)

Mechanical Characteristics

Temperature
UL Temperature
75°C

Standards and Compliance

Environmental Suitability: Outdoor, Sunlight Resistance
NEC / UL Compliance: Article 725, Article 800, CL2, CMG
CEC / C(UL) Compliance: CMG HLBCD

History

Update and Revision: Revision Number: 0.57 Revision Date: 12-22-2023