8678 – Electronic, 2 C #10 Str BC, PVC Ins, PVC Jkt

Call for Price

Description

Product Overview

Suitable Applications: low voltage analog signals (4-20ma, 0-10v, …); low voltage control (24v, …); line level audio

Construction Details

Conductor
Element No. of Elements Size Stranding Material
Conductor(s) 2 10 AWG 19×23 BC – Bare Copper
Insulation
Element Material Nom. Thickness Color Code
Conductor(s) PVC – Polyvinyl Chloride 0.032 in (0.81 mm) Brown, Red
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVC – Polyvinyl Chloride 0.025 in (0.64 mm) 0.225 x 0.400 in
Table Notes: Insulated conductors lay in parallel under jacket

Electrical Characteristics

Electricals
Element Max. Current
Conductor(s) 16 Amps per Conductor at 25ºC
Voltage
Voltage Rating
300 V

Mechanical Characteristics

Temperature
Operating
-20°C to +75°C
Bend Radius
Stationary Min. Installation Min.
2.3 in (58 mm) 2.3 in (58 mm)
Max. Pull Tension: 235.6 lbs (106.9 kg)
Bulk Cable Weight: 95 lbs/1000ft (140 kg/km)

Standards and Compliance

Environmental Suitability: Indoor
European Directive Compliance: EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC Compliance: China RoHS II (GB/T 26572-2011)

History

Update and Revision: Revision Number: 0.331 Revision Date: 02-15-2024

Part Numbers

Variants
Item # Color Putup Type Length UPC Footnote
8678 060500 Chrome Reel 500 ft 612825214045 C